Tupelo |
Code of Ordinances |
Chapter 7. BUILDINGS AND BUILDING REGULATIONS |
Article III. ELECTRICAL CODE |
§ 7-46. Adopted.
The National Electric Code, 2011 Edition is hereby adopted by reference as if fully set herein, with the following exceptions:
(a)
Non-metallic cable in commercial use is restricted to wood frame construction.
(b)
No aluminum wire is allowed inside of building.
(c)
No general purpose or lighting circuits have conductors smaller than #12 AWG.
(d)
Any electrical service of two hundred twenty-five (225) amp rating or less must have a single means of disconnect. Also, any services with more than one means of disconnect must have each means of disconnect labeled with the total number of disconnects installed.
(e)
Other exceptions and modifications included in this chapter.
(Ord. of 9-17-91, § 1; Ord. of 8-4-92, § 1; Ord. of 12-20-94, § 1; Ord. of 11-3-98, § 2; Ord. of 4-2-02(1), § 2; Ord. of 3-9-07, § 2; Ord. of 2-20-18(2) , § 3; Ord. of 9-18-2018(1) )